UPS runtime calculator

List what is plugged into the UPS, then enter the battery details from its label or data sheet. The chart shows how runtime falls as the load rises.

Runs in your browser. Nothing is sent.

Equipment on the UPS
    UPS and batteries
    VA

    300 - 200000 VA

    Power factor
    #

    1 - 64 #

    Voltage per block
    Ah

    1 - 1000 Ah

    #

    Internal pack plus any external battery packs.

    1 - 20 #

    Battery age

    Result

    UPS runtime calculatorLive

    Estimated runtime-
    Total load-W
    Load on the UPS-%

    Runtime as the load changes

    How the UPS runtime calculator works

    UPS real power (W) = rating in VA × power factor. Keeping the load below 80% of that figure leaves room for growth and for the inrush current when equipment starts.

    Battery current I = load ÷ (inverter efficiency × battery voltage), with an efficiency of 90%. Battery voltage = blocks in series × block voltage.

    Runtime uses Peukert's law with an exponent of 1.2, for lead acid batteries with a 20 hour (C20) capacity rating: t = 20 × (C ÷ (I × 20))^1.2 hours, where C is the amp hour capacity of all strings, reduced for battery age. Below the 20 hour current, runtime is taken as C ÷ I.

    Expect the real figure within about 30% of the estimate. Temperature, age and the discharge cut off voltage all move it. The UPS's own runtime chart and a timed test are better sources.

    Planning estimates. They do not replace a measurement on your own systems.

    Terms used here: UPSVA and W

    In practice

    Worked example: two 350 W servers, a 300 W storage unit, two 60 W switches and a 40 W firewall draw 1,160 W. On a 3,000 VA UPS with a power factor of 0.9, that is 43% of its 2,700 W rating. With four 12 V 9 Ah batteries the estimate is about 9 minutes, enough for a clean shutdown but not to ride out a long power cut.

    Runtime falls faster than load rises: halving the load more than doubles the runtime. Old batteries are the most common reason a UPS fails during a real power cut, so record the installation date and test under load once a year.

    Questions about this tool

    How much runtime do we need?

    Enough for servers and storage to shut down cleanly, usually 5 to 10 minutes, plus time for a generator to start if you have one. Longer runtimes need external battery packs.

    Why size by watts and not VA?

    Your equipment draws real power in watts. A UPS with a high VA figure but a low power factor can still be overloaded. Check both figures on the label.

    How accurate is the estimate?

    Within about 30% for healthy lead acid batteries at room temperature. The manufacturer's runtime chart for your exact model is better, and a timed test is best.

    When you want an engineer to look at it

    Planned maintenance

    Monthly checks, patch windows and backup verification by the same engineer, with hours and response times written into the agreement.

    Scope of this service: Planned maintenance

    Tools

    Other tools

    Infrastructure check

    Ten questions on backup, access, power and support. A score out of ten and your three weakest points.

    Downtime cost calculator

    What an outage costs in idle staff, lost revenue and recovery work, per hour, per outage and per year.

    Backup and restore time calculator

    How long the first offsite copy, the daily copies and a full restore take on your links, measured against your recovery targets.